Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 1Owner’s ManualInstallation and OperationModel: QFP44Installation and service of this appliance should
10 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07MantelNon-combustibleFaceAA = 53 in. (1346 mm) min.Non-combustible Mantel12 in. (308 mm) maximum depth
Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 11Horizontaloverhang12X20 in.(508 mm)LowestDischargeOpeningTerminationCapRoof Pitchis X / 12Verticalwa
12 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07Figure 4.4 Minimum Clearances for TerminationsDimension Descriptions A Clearance above the ground, a
Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 13No combustible framing to be located within shaded area. 1-1/2 in. (13 mm)minimum toperpendicularwal
14 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07C. Vertical Penetration FramingNote: An additional ceiling fi restop is not required if attic insulatio
Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 15D. Construct the Appliance ChaseA chase is a vertical boxlike structure built to enclose the gas app
16 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07A. Vent Table KeyThe abbreviations listed in this vent table key are used in the vent diagrams.Symbol
Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 17Fire RiskExplosion RiskDo NOT pack insulation or other combustibles between fi restops.• ALWAYS main
18 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 Top Vent—Horizontal Termination—Two 45° ElbowsInstallation requirements to replace the fi rst 90° elb
Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 1912 ft (3.66 m) min.60 ft (18.29 m) max. Top Vent—Vertical Termination—No Elbows Top Vent—Vertical
2 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07Read this manual before installing or operating this appliance.Please retain this owner’s manual for fu
20 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07Fire Risk!• Prevent contact with sagging, loose insulation.• Do NOT install against combustible mate
Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 21A. Assemble Vent SectionsFigure 8.1 LancesABFigure 8.2 Inner/OuterABFigure 8.3 SnappedCORRECT INC
22 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07Assemble Minimum Installation (MI) SectionsMI sections are non-unitized so that they can be cut to a s
Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 23Secure the Vent SectionsVertical sections of pipe must be supported every 8 ft after the 25 ft maxim
24 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07Burn Risk• Local codes may require installation of a cap shield to prevent anything or anyone from to
Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 25Figure 8.15 Secure with ScrewsD. Install Roof Flashing and Vertical Termination CapTo attach the ve
26 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07E. Assemble and Install Storm CollarConnect both halves of the storm collar with two screws (see Figur
Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 27A. Fuel ConversionBefore making gas connections ensure appliance being in-stalled is compatible with
28 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07Control KnobScrew (pressure adjustment)Pin (blue-NG, red-LP)SolenoidLock NutFigure 9.7 Valve Componen
Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 29Pressure requirements for appliance are shown in table be-low. Minimum pressures must be met when o
Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 3Table of Contents1 Listing and Code Approvals A. Appliance Certifi cation . . . . . . . . . . . . . .
30 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07WARNINGFire RiskExplosion Risk• Gas build-up during line purge may ignite.• Purge should be performe
Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 31A. Connecting to the ApplianceNote: This appliance must be electrically wired and grounded in accord
32 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07B. Junction Box InstallationIf the box is being wired from the OUTSIDE of the appli-ance:• Remove the
Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 33MantelNon-combustibleFaceAA = 53 in. (1346 mm) min.Non-combustible Mantel12 in. (308 mm) maximum dep
34 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07Shock RiskFire RiskUse ONLY optional accessories approved for this appliance.• Using non-listed acces
Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 35• Install the lower back refractory. Figure 12.3 Install Lower Back Refractory• Install the upper
36 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07Figure 12.7 Adjust the Vertical Baffl eFigure 12.8 Positioning Rear LogFigure 12.6 Adjusting the Air
Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 37Figure 12.9 Positioning Ember Bed• Position ember bed over the burner locating the corners inside
38 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07• Place the end of the right middle log on the fl at area on the ember bed and position the hole in th
Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 39H. Place Lava Rock• Cover the visible area of the metal hearth pan around the Ember Bed with a laye
4 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/071 1 Listing and Code Approvals A. Appliance Certifi cationThis product is listed to ANSI standards for “
40 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07Fire RiskAsphyxiation RiskGlass door MUST be in place when appliance is operating. Do NOT operate appl
Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 41C. Remote OperationThis remote control kit has a hand held transmitter that can be used as a remote
42 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07REMOTE RECEIVERThe remote receiver has a 3-position slide switch: OFF/REMOTE/ON (see Figure 13.2).NO
Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 431. LOW - Battery power low. Replace batteries within two weeks.2. TIMER - Indicates time remaining
44 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07Setting °F/°C ScaleThe factory setting for temperature is degrees Fahrenheit °F). To change this setti
Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 45Adjusting the Flame Height -Operates in ON or THERMO modeThis remote control system allows the user
46 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07• Advance the SET temperature on the transmitter to a temperature of at least 2° F (1° C) above the R
Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 47D. Lighting the Appliance1. Turn unit off with remote.2. Turn off all electric power to the applia
48 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07E. After the Appliance is LitInitial Break-in ProcedureWhen you light the appliance, operate on low fo
Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 49With proper installation, operation and maintenance your gas appliance will provide years of trouble
Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 5G. Requirements for the Commonwealth of Mas-sachusettsNOTE: The following requirements reference var
50 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/073. The pilot is burning, there is no burner fl ame, the valve knob is in the ON position, and the MLT O
Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 515. Frequent pilot outage problem.a. Pilot fl ame may be too high or low, or blowing (high), causing p
52 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07Although the frequency of appliance servicing and maintenance will depend on use and the type of insta
Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 53Maintenance and Service Tasks:Inspect Maintenance TasksDoors, surrounds and fronts 1. Access conditi
54 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07A. Appliance Dimension DiagramDimensions are actual appliance dimensions. Use for reference only. For
Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 55B. Vent Components DiagramsComponents DescriptionDVP4 4 in. length Vent PipeDVP6 6 in. length Vent P
56 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07EffectiveLengthDVP Pipe(see chart)Pipe Effective LengthDVP4 4 in. (102 mm)DVP6 6 in. (152 mm)DVP12 12
Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 5713-1/4 in.(367 mm)24-5/8 in.(625 mm)27-1/2 in.(698 mm)RF6MRoof Flashing Multi-pak31 in.(787 mm)24-5/
58 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07DVP-TB1Basement Vent Cap12 in.(305 mm)1-1/2 in.(38 mm)7-3/8 in.(187 mm)14 in.(356 mm)17-3/4 in.(451 mm
Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 59DVP-HPCK2-BDVP-TRAPK1DVP-TRAPK2DVP-HPCK1-BDVP-TRAPHorizontal Termination Cap15-1/8 in.(384 mm)12 in.
6 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07A. Design and Installation ConsiderationsQuadra-Fire direct vent gas appliances are designed to op-erat
60 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07C. Service Parts List11110141291820133241716157858196QFP44Service PartsExploded Parts Diagram Beginni
Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 61Service Parts List44 in. Gas Appliance - DV(parts listed in bold italics are critical parts)Service
62 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07QFP44 Service PartsExploded Parts Diagram Beginning Manufacturing Date: 8/1/0644 in. Gas Appliance -
Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 63Service Parts List44 in. Gas Appliance - DV(parts listed in bold italics are critical parts)Service
64 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07QFP44 Service PartsExploded Parts Diagram Beginning Manufacturing Date: 8/1/0644 in. Gas Appliance -
Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 65Service Parts List44 in. Gas Appliance - DV(parts listed in bold italics are critical parts)Service
66 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07D. Optional ComponentsDoor (iron full view) DF-QFP44-IFVDoor (iron operable) DF-QFP44-IOPDoor (Craftsm
Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 67E. Limited Lifetime WarrantyLIMITED LIFETIME WARRANTYThe Hearth & Home Technologies limited Life
68 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07F. Contact Information- NOTES -DO NOT DISCARD THIS MANUALCAUTION• Important operating and maintenance
Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 745231Figure 2.2 Logs on TopRefractoryShipping BracketsAndironsFigure 2.1 Refractory Shipping Locati
8 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/0752 in.(1321 mm)1.5 in. (114 mm)1.5 in.(114 mm)31 in.(787 mm)69-3/4 in.(1772 mm)69-3/4 in.(1772 mm)1.5 i
Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 9B. ClearancesCombustible flooring may be installed next to the front of the appliance. ALL SURFACES M