Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 1
Owners Manual
Installation and Operation
Model:
QFP44
Installation and service of this appliance should be performed
by qualified personnel. Hearth & Home Technologies
suggests NFI certi ed or factory-trained
professionals, or technicians supervised
by an NFI certi ed professional.
If the information in these instruc-
tions is not followed exactly, a
re may result causing property
damage, personal injury, or death.
Do not store or use gasoline or other am-
mable vapors and liquids in the vicinity of
this or any other appliance.
What to do if you smell gas:
- Do
not try to light any appliance.
- Do not touch any electrical switch. Do not
use any phone in your building.
- Immediately call your gas supplier from
a neighbor’s phone. Follow the gas
supplier’s instructions.
- If you cannot reach your gas supplier, call
the re department.
Installation and service must be performed
by a quali ed installer, service agency, or
the gas supplier.
WARNING
HOT! DO NOT TOUCH.
SEVERE BURNS MAY RESULT.
CLOTHING IGNITION MAY RESULT.
WARNING
Keep children away.
CAREFULLY SUPERVISE children in same room as
appliance.
Alert children and adults to hazards of high
temperatures.
Do NOT operate with protective barriers removed or
door open.
Keep clothing, furniture, draperies and other
combustibles away.
Glass and other surfaces are hot during
operation and cool down.
This appliance may be installed as an OEM installation
in manufactured home (USA only) or mobile home and
must be installed in accordance with the manufacturer’s
instructions and the manufactured home construction and
safety standard, Title 24 CFR, Part 3280 or Standard for
Installation in Mobile Homes, CAN/CSA Z240MH.
This appliance is only for use with the type(s) of gas indicated
on the rating plate. A conversion kit is supplied with the
appliance.
DO NOT DISCARD THIS MANUAL
CAUTION
Important operating and
maintenance instructions
included.
Leave this manual with
party responsible for
use and operation.
Read, understand and follow
these instructions for safe
installation and operation.
DO NOT
DISCARD
In the Commonwealth of Massachusetts:
installation must be performed by a licensed plumber or
gas tter;
See Table of Contents for location of additional
Commonwealth of Massachusetts requirements.
Page view 0
1 2 3 4 5 6 ... 67 68

Summary of Contents

Page 1 - Owner’s Manual

Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 1Owner’s ManualInstallation and OperationModel: QFP44Installation and service of this appliance should

Page 2 - GA000001

10 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07MantelNon-combustibleFaceAA = 53 in. (1346 mm) min.Non-combustible Mantel12 in. (308 mm) maximum depth

Page 3 - Table of Contents

Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 11Horizontaloverhang12X20 in.(508 mm)LowestDischargeOpeningTerminationCapRoof Pitchis X / 12Verticalwa

Page 4 - Listing and Code Approvals

12 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07Figure 4.4 Minimum Clearances for TerminationsDimension Descriptions A Clearance above the ground, a

Page 5 - Massachusetts

Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 13No combustible framing to be located within shaded area. 1-1/2 in. (13 mm)minimum toperpendicularwal

Page 6 - Getting Started

14 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07C. Vertical Penetration FramingNote: An additional ceiling fi restop is not required if attic insulatio

Page 7 - Andirons

Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 15D. Construct the Appliance ChaseA chase is a vertical boxlike structure built to enclose the gas app

Page 8 - Framing and Clearances

16 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07A. Vent Table KeyThe abbreviations listed in this vent table key are used in the vent diagrams.Symbol

Page 9 - B. Clearances

Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 17Fire RiskExplosion RiskDo NOT pack insulation or other combustibles between fi restops.• ALWAYS main

Page 10 - D. Non-Combustible Zone

18 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 Top Vent—Horizontal Termination—Two 45° ElbowsInstallation requirements to replace the fi rst 90° elb

Page 11 - Termination Caps Same Height

Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 1912 ft (3.66 m) min.60 ft (18.29 m) max. Top Vent—Vertical Termination—No Elbows Top Vent—Vertical

Page 12

2 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07Read this manual before installing or operating this appliance.Please retain this owner’s manual for fu

Page 13 - Vent Clearances and Framing

20 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07Fire Risk!• Prevent contact with sagging, loose insulation.• Do NOT install against combustible mate

Page 14 - 3 fasteners

Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 21A. Assemble Vent SectionsFigure 8.1 LancesABFigure 8.2 Inner/OuterABFigure 8.3 SnappedCORRECT INC

Page 15

22 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07Assemble Minimum Installation (MI) SectionsMI sections are non-unitized so that they can be cut to a s

Page 16 - C. Measuring Standards

Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 23Secure the Vent SectionsVertical sections of pipe must be supported every 8 ft after the 25 ft maxim

Page 17 - D. Vent Diagrams

24 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07Burn Risk• Local codes may require installation of a cap shield to prevent anything or anyone from to

Page 18 - Vertically

Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 25Figure 8.15 Secure with ScrewsD. Install Roof Flashing and Vertical Termination CapTo attach the ve

Page 19 - 60 ft (18.29 m) max

26 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07E. Assemble and Install Storm CollarConnect both halves of the storm collar with two screws (see Figur

Page 20 - Appliance Preparation

Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 27A. Fuel ConversionBefore making gas connections ensure appliance being in-stalled is compatible with

Page 21 - Installing Vent Pipe

28 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07Control KnobScrew (pressure adjustment)Pin (blue-NG, red-LP)SolenoidLock NutFigure 9.7 Valve Componen

Page 22 - Assemble Slip Sections

Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 29Pressure requirements for appliance are shown in table be-low. Minimum pressures must be met when o

Page 23 - B. Disassemble Vent Sections

Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 3Table of Contents1 Listing and Code Approvals A. Appliance Certifi cation . . . . . . . . . . . . . .

Page 24 - Termination

30 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07WARNINGFire RiskExplosion Risk• Gas build-up during line purge may ignite.• Purge should be performe

Page 25 - Flashing

Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 31A. Connecting to the ApplianceNote: This appliance must be electrically wired and grounded in accord

Page 26 - Sharp Edges!

32 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07B. Junction Box InstallationIf the box is being wired from the OUTSIDE of the appli-ance:• Remove the

Page 27 - Gas Information

Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 33MantelNon-combustibleFaceAA = 53 in. (1346 mm) min.Non-combustible Mantel12 in. (308 mm) maximum dep

Page 28 - Lock Nut

34 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07Shock RiskFire RiskUse ONLY optional accessories approved for this appliance.• Using non-listed acces

Page 29 - C. Gas Connection

Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 35• Install the lower back refractory. Figure 12.3 Install Lower Back Refractory• Install the upper

Page 30 - CHECK FOR GAS LEAKS

36 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07Figure 12.7 Adjust the Vertical Baffl eFigure 12.8 Positioning Rear LogFigure 12.6 Adjusting the Air

Page 31 - Electrical Information

Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 37Figure 12.9 Positioning Ember Bed• Position ember bed over the burner locating the corners inside

Page 32 - Finishing

38 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07• Place the end of the right middle log on the fl at area on the ember bed and position the hole in th

Page 33 - C. Door Installation

Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 39H. Place Lava Rock• Cover the visible area of the metal hearth pan around the Ember Bed with a laye

Page 34 - Appliance Setup

4 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/071 1 Listing and Code Approvals A. Appliance Certifi cationThis product is listed to ANSI standards for “

Page 35

40 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07Fire RiskAsphyxiation RiskGlass door MUST be in place when appliance is operating. Do NOT operate appl

Page 36 - E. Adjust the Vertical Baffl e

Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 41C. Remote OperationThis remote control kit has a hand held transmitter that can be used as a remote

Page 37

42 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07REMOTE RECEIVERThe remote receiver has a 3-position slide switch: OFF/REMOTE/ON (see Figure 13.2).NO

Page 38 - G. Install Andirons

Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 431. LOW - Battery power low. Replace batteries within two weeks.2. TIMER - Indicates time remaining

Page 39 - J. Install Door Fronts

44 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07Setting °F/°C ScaleThe factory setting for temperature is degrees Fahrenheit °F). To change this setti

Page 40 - Operating Instructions

Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 45Adjusting the Flame Height -Operates in ON or THERMO modeThis remote control system allows the user

Page 41 - Ignitor Battery Box

46 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07• Advance the SET temperature on the transmitter to a temperature of at least 2° F (1° C) above the R

Page 42 - OFF-REMOTE-ON GROUND VALVE

Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 47D. Lighting the Appliance1. Turn unit off with remote.2. Turn off all electric power to the applia

Page 43 - OPERATING INSTRUCTIONS

48 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07E. After the Appliance is LitInitial Break-in ProcedureWhen you light the appliance, operate on low fo

Page 44 - Setting the Countdown Timer

Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 49With proper installation, operation and maintenance your gas appliance will provide years of trouble

Page 45 - SYSTEM CHECK

Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 5G. Requirements for the Commonwealth of Mas-sachusettsNOTE: The following requirements reference var

Page 46 - GENERAL INFORMATION

50 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/073. The pilot is burning, there is no burner fl ame, the valve knob is in the ON position, and the MLT O

Page 47 - THERMOCOUPLE

Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 515. Frequent pilot outage problem.a. Pilot fl ame may be too high or low, or blowing (high), causing p

Page 48 - F. Frequently Asked Questions

52 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07Although the frequency of appliance servicing and maintenance will depend on use and the type of insta

Page 49 - Troubleshooting

Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 53Maintenance and Service Tasks:Inspect Maintenance TasksDoors, surrounds and fronts 1. Access conditi

Page 50

54 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07A. Appliance Dimension DiagramDimensions are actual appliance dimensions. Use for reference only. For

Page 51

Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 55B. Vent Components DiagramsComponents DescriptionDVP4 4 in. length Vent PipeDVP6 6 in. length Vent P

Page 52

56 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07EffectiveLengthDVP Pipe(see chart)Pipe Effective LengthDVP4 4 in. (102 mm)DVP6 6 in. (152 mm)DVP12 12

Page 53 - Inspect Maintenance Tasks

Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 5713-1/4 in.(367 mm)24-5/8 in.(625 mm)27-1/2 in.(698 mm)RF6MRoof Flashing Multi-pak31 in.(787 mm)24-5/

Page 54 - Reference Materials

58 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07DVP-TB1Basement Vent Cap12 in.(305 mm)1-1/2 in.(38 mm)7-3/8 in.(187 mm)14 in.(356 mm)17-3/4 in.(451 mm

Page 55 - B. Vent Components Diagrams

Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 59DVP-HPCK2-BDVP-TRAPK1DVP-TRAPK2DVP-HPCK1-BDVP-TRAPHorizontal Termination Cap15-1/8 in.(384 mm)12 in.

Page 56 - (see chart)

6 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07A. Design and Installation ConsiderationsQuadra-Fire direct vent gas appliances are designed to op-erat

Page 57

60 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07C. Service Parts List11110141291820133241716157858196QFP44Service PartsExploded Parts Diagram Beginni

Page 58

Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 61Service Parts List44 in. Gas Appliance - DV(parts listed in bold italics are critical parts)Service

Page 59

62 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07QFP44 Service PartsExploded Parts Diagram Beginning Manufacturing Date: 8/1/0644 in. Gas Appliance -

Page 60 - Service Parts

Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 63Service Parts List44 in. Gas Appliance - DV(parts listed in bold italics are critical parts)Service

Page 61

64 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07QFP44 Service PartsExploded Parts Diagram Beginning Manufacturing Date: 8/1/0644 in. Gas Appliance -

Page 62

Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 65Service Parts List44 in. Gas Appliance - DV(parts listed in bold italics are critical parts)Service

Page 63

66 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07D. Optional ComponentsDoor (iron full view) DF-QFP44-IFVDoor (iron operable) DF-QFP44-IOPDoor (Craftsm

Page 64

Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 67E. Limited Lifetime WarrantyLIMITED LIFETIME WARRANTYThe Hearth & Home Technologies limited Life

Page 65

68 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07F. Contact Information- NOTES -DO NOT DISCARD THIS MANUALCAUTION• Important operating and maintenance

Page 66 - D. Optional Components

Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 745231Figure 2.2 Logs on TopRefractoryShipping BracketsAndironsFigure 2.1 Refractory Shipping Locati

Page 67 - Lifetime Warranty

8 Quadra-Fire • QFP44 • 4051-300 Rev F • 02/0752 in.(1321 mm)1.5 in. (114 mm)1.5 in.(114 mm)31 in.(787 mm)69-3/4 in.(1772 mm)69-3/4 in.(1772 mm)1.5 i

Page 68 - DO NOT DISCARD THIS MANUAL

Quadra-Fire • QFP44 • 4051-300 Rev F • 02/07 9B. ClearancesCombustible flooring may be installed next to the front of the appliance. ALL SURFACES M