13
Figure 5. Framing Dimensions
Framing should be
constructed of 2 X 4
lumber or heavier.
WARNING:
To ensure proper clearances the front
framing header must be installed on its
narrow edge and to the front of the frame.
The framing headers may rest
on the fireplace stand-offs.
VENT
FRAMING
HOLE
E
D
Model A B C D E *
QV36-A 42” 38 1/4” 16 1/4” 41” 27 7/8”
QV32-A 37” 33” 16 1/4” 36 1/2” 24 3/8”
B
Step 2. Framing the Fireplace
Fireplace framing can be built before or after the fireplace
is set in place. Framing should be positioned to accommo-
date wall coverings and fireplace facing material. The dia-
gram below shows framing reference dimensions.
CAUTION: MEASURE FIREPLACE DIMENSIONS AND
VERIFY FRAMING METHODS AND WALL COVERING
DETAILS BEFORE FRAMING.
*The center of the framing hole is one (1)
inch (25.4mm) above the center of the
horizontal vent pipe.
WALL STUD
IS DEFINED BY 3” ABOVE THE
ELBOW FOR THE ENTIRE
WIDTH AND DEPTH (BEHIND THE
FRONT HEADER) OF THE FIREBOX.
3 1/2”
u